How to read the result
- What the number is: the smallest liquid capacity the state rule allows for a single-family home with 3 bedrooms: 1,000 gal (3,785 L) under Washington WAC 246-272A-0232. It is a legal floor, not the best size for your family.
- Why bedrooms: state rules count bedrooms as a stand-in for the flow the house can produce, whatever the number of people living there today. A study or office that could be a bedroom may count as one.
- States differ: for 5 bedrooms Washington asks 1,250 gal, Wyoming 1,150 gal and Arizona 1,500 gal at 35 fixtures or fewer. That is why the page applies one named state rule at a time and shows its date, and gives no number for a state it has not read.
- What is not here: the drainfield or leach field, soil and percolation tests, pump tanks, water table and setbacks, county rules, and the permit itself. The tank is only one part of the system.
The tank is only one part of the system. To find the volume of a tank from its own dimensions, use the Water Tank Volume Calculator.
Worked example
A family plans a 3-bedroom house in Washington and is quoted a 1,000 gal tank.
- Rule: Washington WAC 246-272A-0232 Table VII, effective 1 April 2025 (WSR 24-06-046): up to 4 bedrooms, 1,000 gal
- Minimum liquid capacity = 1,000 gal = 3,785 L (1 gal = 3.785411784 L)
- Tank check: 1,000 gal is 1,000 gal: at or above the minimum. That is not an approval: the county decides.
- With 6 bedrooms: 1,000 + 250 × (6 − 4) = 1,500 gal
- The same 3-bedroom house in Wyoming: 1,000 gal; in Arizona with 21 fixtures or fewer: 1,000 gal (design flow 450 gal/day), and with 22 fixtures: 1,250 gal (design flow 600 gal/day)
These are the same numbers the calculator shows when it first loads.
Method and formulas
Washington: V = 1,000 gal (up to 4 bedrooms); V = 1,000 + 250 × (bedrooms − 4) gal above that
Wyoming: V = 1,000 gal (up to 4 bedrooms); V = 1,000 + 150 × (bedrooms − 4) gal above that
Arizona: V and design flow read from the R18-9-A314 table by bedrooms and by whether the fixture count is above 7 × bedrooms
- V
- Minimum septic tank liquid capacity, in US gallons (litres), as the state rule prints it
- Bedrooms
- Bedrooms the single-family house is designed or permitted for
- Fixtures
- Arizona only: the plumbing fixture count under R18-9-A314(4)(a)(ii)
Each rule is a state regulation read on 2 November 2026 with its effective date shown beside every result. Rules change, and counties can be stricter: check the current text with your county health department.
Assumptions and limits
- Single-family home; the reader enters the permitted bedroom count.
- Each state value is the rule's minimum liquid capacity as printed, not a recommendation.
- The page applies one state rule at a time; it never averages or blends states.
- Gallons are US liquid gallons.
- Minimum tank capacity only: not the drainfield or leach field, soil tests, pump tanks, water table, setbacks or the whole system.
- Four listed states at launch; other states return no number and a plain explanation of what to ask.
- Counties, cities and special districts can set stricter rules than the state.
- Not a permit, an approval, a design or a substitute for a licensed designer or the local health department.
- Not for commercial, shared or multi-family systems.
- Rules change; each result shows the edition used and the date it was checked.
Reference tables
| Bedrooms | Minimum liquid volume | How |
|---|---|---|
| 1 | 1,000 gal | Table minimum |
| 2 | 1,000 gal | Table minimum |
| 3 | 1,000 gal | Table minimum |
| 4 | 1,000 gal | Table minimum |
| 5 | 1,250 gal | 1,000 + 250 × 1 |
| 6 | 1,500 gal | 1,000 + 250 × 2 |
| 7 | 1,750 gal | 1,000 + 250 × 3 |
| 8 | 2,000 gal | 1,000 + 250 × 4 |
Source: Washington Administrative Code 246-272A-0232, Table VII (effective 1 April 2025 (WSR 24-06-046)): up to 4 bedrooms 1,000 gal; each additional bedroom 250 gal.
| Bedrooms | Minimum liquid volume | How |
|---|---|---|
| 1 | 1,000 gal | Rule minimum |
| 2 | 1,000 gal | Rule minimum |
| 3 | 1,000 gal | Rule minimum |
| 4 | 1,000 gal | Rule minimum |
| 5 | 1,150 gal | 1,000 + 150 × 1 |
| 6 | 1,300 gal | 1,000 + 150 × 2 |
| 7 | 1,450 gal | 1,000 + 150 × 3 |
| 8 | 1,600 gal | 1,000 + 150 × 4 |
Source: Wyoming Water Quality Rules and Regulations, ch. 25 sec. 10(a)(iii)(A) (amended effective 29 June 2018): 1,000 gal for up to 4 bedrooms; 150 gal for each bedroom over 4.
| Bedrooms | Fixture count | Minimum design liquid capacity | Design flow |
|---|---|---|---|
| 1 | 7 or fewer | 1,000 gal | 150 gal/day |
| 1 | More than 7 | 1,000 gal | 300 gal/day |
| 2 | 14 or fewer | 1,000 gal | 300 gal/day |
| 2 | More than 14 | 1,000 gal | 450 gal/day |
| 3 | 21 or fewer | 1,000 gal | 450 gal/day |
| 3 | More than 21 | 1,250 gal | 600 gal/day |
| 4 | 28 or fewer | 1,250 gal | 600 gal/day |
| 4 | More than 28 | 1,500 gal | 750 gal/day |
| 5 | 35 or fewer | 1,500 gal | 750 gal/day |
| 5 | More than 35 | 2,000 gal | 900 gal/day |
| 6 | 42 or fewer | 2,000 gal | 900 gal/day |
| 6 | More than 42 | 2,500 gal | 1,050 gal/day |
| 7 | 49 or fewer | 2,500 gal | 1,050 gal/day |
| 7 | More than 49 | 3,000 gal | 1,200 gal/day |
| 8 | 56 or fewer | 3,000 gal | 1,200 gal/day |
| 8 | More than 56 | 3,000 gal | 1,350 gal/day |
Source: Arizona Administrative Code R18-9-A314(4)(a)(i) (amended effective 19 June 2023), single-family dwellings.
| Bedrooms | Washington | Wyoming | Arizona, few fixtures | Arizona, many fixtures |
|---|---|---|---|---|
| 1 | 1,000 | 1,000 | 1,000 | 1,000 |
| 2 | 1,000 | 1,000 | 1,000 | 1,000 |
| 3 | 1,000 | 1,000 | 1,000 | 1,250 |
| 4 | 1,000 | 1,000 | 1,250 | 1,500 |
| 5 | 1,250 | 1,150 | 1,500 | 2,000 |
| 6 | 1,500 | 1,300 | 2,000 | 2,500 |
| 7 | 1,750 | 1,450 | 2,500 | 3,000 |
| 8 | 2,000 | 1,600 | 3,000 | 3,000 |
Source: Washington WAC 246-272A-0232 (effective 1 April 2025 (WSR 24-06-046)); Wyoming Water Quality Rules ch. 25 sec. 10 (amended effective 29 June 2018); Arizona R18-9-A314 (amended effective 19 June 2023). Read on 2 Nov 2026. Worked out by the EngiFormula septic tank engine.
Charts and diagrams
Show chart data as a table
| Bedrooms | Washington | Wyoming | Arizona (few fixtures) |
|---|---|---|---|
| 1 | 1,000 | 1,000 | 1,000 |
| 2 | 1,000 | 1,000 | 1,000 |
| 3 | 1,000 | 1,000 | 1,000 |
| 4 | 1,000 | 1,000 | 1,250 |
| 5 | 1,250 | 1,150 | 1,500 |
| 6 | 1,500 | 1,300 | 2,000 |
| 7 | 1,750 | 1,450 | 2,500 |
| 8 | 2,000 | 1,600 | 3,000 |
Source: Washington WAC 246-272A-0232 (effective 1 April 2025 (WSR 24-06-046)); Wyoming Water Quality Rules ch. 25 sec. 10 (amended effective 29 June 2018); Arizona R18-9-A314 (amended effective 19 June 2023). Read on 2 Nov 2026. Worked out by the EngiFormula septic tank engine.
Common uses
Before you call an installer
Know the minimum your state's rule sets for your bedroom count, so a quote can be compared with it.
Checking a quote
Enter the maker's stated liquid capacity to see whether it is below or at or above the minimum.
Planning an extra bedroom
Run the bedroom count before and after to see how the state minimum moves.
Comparing states
See how the same house is treated by the rules of the listed states.
Frequently asked questions
What size septic tank do I need for a 3-bedroom house?
It depends on the state. For 3 bedrooms the listed states give 1,000 gal in Washington, 1,000 gal in Wyoming and 1,000 gal in Arizona (with 1,250 gal in Arizona above 21 fixtures). The county or health department can ask for more, and the rule text on this page shows the date it was read.
How is septic tank size calculated?
In the listed states the rule sets a minimum liquid capacity from the number of bedrooms, and in Arizona also from the fixture count. This page applies the rule as printed; there is no national formula, so it gives no number for a state it has not read.
Is a 1,000 gallon septic tank big enough?
1,000 gal is the minimum in Washington and Wyoming up to 4 bedrooms and in Arizona up to 3 bedrooms with 21 fixtures or fewer. Above that the minimum rises (1,250 gal for 5 bedrooms in Washington). A minimum is a floor, not the best size, and the local authority decides.
Does septic tank size depend on the number of people or bedrooms?
US state rules use bedrooms (and in Arizona fixtures) as a stand-in for the flow the house can produce. Some countries size by users instead; this page does not.
Do all states use the same septic tank size rules?
No. For 5 bedrooms Washington asks 1,250 gal, Wyoming 1,150 gal and Arizona 1,500 gal at 35 fixtures or fewer. Pick the state where the house is built; counties may be stricter.
What is the difference between a septic tank and a drainfield?
The tank settles solids and holds the wastewater for a time; the drainfield sends the liquid into the soil and is sized from soil tests. This page covers only the minimum tank capacity.
Can I use this calculator to get a permit?
No. It is a planning reference, not a permit, a design or an approval. The permit and design come from the local health department and a licensed designer.
Sources and references
- Washington State Department of Health, WAC 246-272A-0232, Septic tank design, Table VII, effective 1 April 2025 (WSR 24-06-046).
- State of Wyoming, Water Quality Rules and Regulations, Chapter 25, Section 10, amended effective 29 June 2018.
- Arizona Department of Environmental Quality, Arizona Administrative Code R18-9-A314, amended effective 19 June 2023.
- NIST Special Publication 811, Guide for the Use of the International System of Units (SI), 2008 edition, Appendix B (the US gallon in litres).
About this calculator
Scope and disclaimer
The state-rule minimum septic tank liquid capacity for a single-family home, by bedrooms, for the listed states, with an optional check of a tank size. It is not a drainfield or leach field calculator, a soil test tool, a pump tank sizer, a permit or an approval.
This calculator gives information and preliminary estimates only. It is not professional design advice and does not replace the governing code, product instructions or a qualified professional's judgement for your project.