Hazen-Williams Calculator

Enter the flow, the pipe and its C factor to get the friction head loss and pressure drop of water, or solve backwards for the flow or the pipe diameter a head loss you can afford allows.

  • Cited C factor table (NRCS)
  • Solves head loss, flow or pipe size
  • Turbulence check
  • C sensitivity table
  • US and metric

Enter the pipe and what you know

Units
gpm
in
ft
°F

Use the inside diameter of the pipe, not the nominal size.

Measured along the pipe, straight pipe only. Fittings and valves are not counted.

C values are from NRCS National Engineering Handbook Part 634 Chapter 4, Figure 4-8. A lower C means more friction. The handbook gives typical values, not exact ones.

Figure 4-8 runs from 40 (small, old, rough pipe) to 150 (plastic).

The Hazen-Williams result does not change with temperature. It is used only to check that the flow is turbulent and to turn head into pressure.

Friction head loss over the length

10.72 ft

Friction head loss
10.72 ft
Flow rate
100 gpm
Pipe inside diameter
3.068 in
Head loss per 100 of length
2.14 ft per 100 ft
Energy slope
0.0214
Pressure drop
4.64 psi
Mean velocity
4.34 ft/s
Reynolds number
102,681
Flow regime
Turbulent
C factor used
150

100 gpm through 500 ft of 3.068 in pipe (PVC, PE or HDPE, C = 150) loses 10.72 ft of head to friction, 2.14 ft per 100 ft, a pressure drop of 4.64 psi, at a velocity of 4.34 ft/s.

Show the working

  1. C factor for PVC, PE or HDPE (NRCS Figure 4-8) = 150
  2. Friction head loss = 10.704 × (flow ÷ C)^1.85 × length ÷ diameter^4.87, in metres and cubic metres per second = 10.72 ft
  3. Energy slope = head loss ÷ length; per 100 of length = 2.14 ft per 100 ft
  4. Velocity = flow ÷ (π × (3.068 in)² ÷ 4) = 4.34 ft/s
  5. Pressure drop = density (998.1 kg/m³) × g (9.80665 m/s²) × head loss = 4.64 psi
  6. Reynolds number = density × velocity × diameter ÷ viscosity (1.002 mPa·s) = 102,681

What you can do with this calculator

  1. Hazen-Williams calculator. Friction head loss and pressure drop for water in a pipe.
  2. Hazen-Williams friction loss. Loss per 100 ft for your flow, pipe size and C.
  3. Solve backwards. The flow, or the pipe size, a loss you can afford allows.
  4. Pick the C factor from a cited table. See how much the answer moves with it.
  5. Check the formula suits the case. The Reynolds number tells you if the flow is turbulent.

How to read the result

  • What the C factor is: a single number for the pipe wall. The NRCS handbook lists typical values by material and age: 150 for PVC, PE and HDPE, 130 for new cast iron or steel, 100 for the same pipe at 15 years old. The lower the C, the more friction. For 100 gpm through 500 ft of 3.068 in pipe, C 150 gives 10.72 ft, C 120 gives 16.20 ft and C 100 gives 22.69 ft.
  • Why flow matters most: head loss grows with the flow to the power 1.85, so doubling the flow to 200 gpm multiplies the loss by 3.61, from 10.72 ft to 38.64 ft. It falls steeply as the pipe grows, with the diameter to the power 4.87.
  • Head loss, slope and pressure: the head loss is the total over your length. Divided by the length it is the energy slope (0.0214), and per 100 ft it is 2.14 ft per 100 ft. One foot of water head is 0.433 psi, so 10.72 ft is 4.64 psi.
  • The Reynolds number check: Hazen-Williams was fitted to water in turbulent flow. The page works out the Reynolds number (102,681 here, turbulent) and warns when it falls below 4,000, where the equation does not hold.
  • Compared with Darcy-Weisbach: for the same flow, PVC pipe and water at 68 °F, the Pipe Friction Loss Calculator gives 10.32 ft, so Hazen-Williams reads 3.9% higher in this case. The two methods rarely agree exactly, because C is a typical value.
  • What this page leaves out: fittings, valves, entrance and exit losses, the lift (static head), liquids other than water, and fire-sprinkler or other code design. Add fitting losses separately.

To get the same loss by Darcy-Weisbach, for any liquid or any flow regime, use the Pipe Friction Loss Calculator. To add the lift and the outlet pressure and get the head a pump must deliver, use the Pump Total Dynamic Head Calculator. This page gives the friction of the straight pipe for water in turbulent flow; it leaves out fittings, valves and elevation, and it is not a fire-sprinkler or code design.

Worked example

Water at 68 °F (20 °C) flows at 100 gpm through 500 ft of PVC pipe with an inside diameter of 3.068 in (the inside diameter of 3 in schedule 40 pipe, typed in as an example). The NRCS table gives C = 150 for PVC, PE and HDPE.

  1. Flow = 100 gpm = 6.309 L/s; inside diameter = 3.068 in = 77.9 mm; length = 500 ft = 152.4 m
  2. Friction head loss = 10.704 × (flow ÷ C)1.85 × length ÷ diameter4.87, in metres and m³/s, = 10.72 ft (3.27 m)
  3. Per 100 ft: head loss ÷ length × 100 = 2.14 ft per 100 ft
  4. Velocity = flow ÷ (π × D² ÷ 4) = 4.34 ft/s (1.32 m/s)
  5. Pressure drop = density × g × head loss = 4.64 psi (31.98 kPa)
  6. Reynolds number = 102,681, turbulent, so the equation applies
  7. The same pipe at C 120 (steel, 5 years old): 16.20 ft; at C 100: 22.69 ft
  8. Solving the other way: with 10 ft of head loss allowed over the same 500 ft, the pipe carries 96.32 gpm; for half the head loss (5.36 ft) at 100 gpm it needs an inside diameter of at least 3.54 in

The same pipe by Darcy-Weisbach (the method of the Pipe Friction Loss page, PVC roughness) gives 10.32 ft, so Hazen-Williams with C = 150 reads 3.9% higher.

These are the same numbers the calculator shows when it first loads.

Method and formulas

hf = 10.704 · (Q ÷ C)1.85 · L ÷ D4.87   (hf, L, D in m; Q in m³/s)
Q = C · (hf · D4.87 ÷ (10.704 · L))1 ÷ 1.85
D = (10.704 · L · (Q ÷ C)1.85 ÷ hf)1 ÷ 4.87
V = Q ÷ (π D² ÷ 4) · S = hf ÷ L · Δp = ρ g hf · Re = ρ V D ÷ μ

hf
Friction head loss over the length, in feet (metres) of water
Q
Flow rate
C
Hazen-Williams coefficient from Figure 4-8 of the NRCS handbook, or the value you enter
L, D
Pipe length and inside diameter
V, S
Mean velocity and energy slope
ρ, μ, g
Density and viscosity of water at your temperature, and 9.80665 m/s²

The NRCS handbook (634.0404) gives the Hazen-Williams formula as V = 0.849 C R0.63 S0.54 in SI units and, solved for the head loss from the discharge, hf = 10.704 (Q ÷ C)1.85 L ÷ D4.87 (equation 4-27). The page uses that form in SI and converts, so the US and metric inputs always give the same physical result. The handbook prints a different constant for US units (4.732 with feet and cubic feet per second), which reads about 0.8% lower for the same pipe; other sites use 10.67 with exponents 1.852 and 4.8704, which reads about 1.4% lower than this page for the default case. Solving for the flow or the diameter uses the same equation rearranged, so the three modes agree exactly. The Reynolds number uses the density and viscosity of water from the handbook’s table (Chapter 1, Figure 1-9), and the regimes of Chapter 4: laminar below 2,000, transitional from 2,000 to 4,000, turbulent above.

Assumptions and limits

  • Water at ordinary temperatures in a full, circular pipe flowing under pressure at a steady rate; the handbook gives Hazen-Williams as an empirical formula from water-flow data.
  • The result depends on the C factor only (not on temperature); C is chosen by the reader from the handbook table or typed.
  • Friction in the straight pipe only: fittings, valves and entrance losses are not included (the handbook treats local losses as a separate K·v²/2g term and neglects them in its Hazen-Williams examples).
  • Static (elevation) head is not part of the result: only the friction head loss and the pressure drop it causes.
  • Solving for flow or diameter uses the same equation rearranged, so the three modes agree.
  • Water only: oils, chemicals, slurries and gases need Darcy-Weisbach, which the Pipe Friction Loss page uses.
  • The handbook gives typical C values, not exact ones; pipe ages and deposits move C a lot, so the page shows how head loss changes with C.
  • Flow below Reynolds number 4,000 (laminar or transitional): the page shows the result with a warning that Hazen-Williams does not hold there.
  • Not a fire-sprinkler, fire-pump or code design calculation: those follow NFPA and the authority having jurisdiction, with their own C factors and checks.
  • The handbook gives no limit on pipe size or velocity: the page shows the velocity and leaves the limit to the reader and the project rules.

Reference tables

Hazen-Williams C factor by pipe material and condition (typical values)
Pipe and conditionC
PVC, PE or HDPE150
Very smooth, straight alignment140
Very smooth, slight curvature130
Brass or lead, new140
Asbestos cement140
Cast iron uncoated or steel, new130
Cast iron uncoated or steel, 5 years old120
Cast iron uncoated or steel, 10 years old110
Cast iron uncoated or steel, 15 years old100
Cast iron uncoated or steel, 20 years old90
Cast iron uncoated or steel, 30 years old80
Cast iron, coated, all ages130
Concrete, very smooth, excellent joints140
Concrete, smooth, good joints120
Concrete, rough110
Vitrified clay110
Smooth wood or wood stave120
Wrought iron or galvanized steel, 12 in and larger110
Wrought iron or galvanized steel, 4 to 12 in100
Wrought iron or galvanized steel, 4 in or less80
Aluminum120
Aluminum gated pipe110
Corrugated metal60

Source: USDA Natural Resources Conservation Service, National Engineering Handbook Part 634 Hydraulics, Chapter 4 Pipe Flow, 1st Edition, February 2022, section 634.0404, equations 4-21 to 4-30 and Figure 4-8 (values of the Hazen-Williams coefficient, page 634-4.12).

Head loss in feet per 100 ft of pipe with C = 150, by flow and inside diameter
Flow2 in3 in4 in6 in
50 gpm4.780.660.160.02
100 gpm17.222.390.590.08
150 gpm36.475.061.250.17
200 gpm62.098.622.120.29
300 gpm131.4718.254.500.62

Source: USDA Natural Resources Conservation Service, National Engineering Handbook Part 634 Hydraulics, Chapter 4 Pipe Flow, 1st Edition, February 2022, section 634.0404, equations 4-21 to 4-30 and Figure 4-8 (values of the Hazen-Williams coefficient, page 634-4.12). Head losses worked out by the EngiFormula engine with C = 150.

How the head loss changes with C for 100 gpm through 500 ft of 3.068 in pipe
C factorHead loss over 500 ftCompared with C 150Pressure drop
8034.29 ft320%14.84 psi
9027.58 ft257%11.93 psi
10022.69 ft212%9.82 psi
11019.03 ft177%8.23 psi
12016.20 ft151%7.01 psi
13013.97 ft130%6.04 psi
14012.18 ft114%5.27 psi
15010.72 ft100%4.64 psi

Source: USDA Natural Resources Conservation Service, National Engineering Handbook Part 634 Hydraulics, Chapter 4 Pipe Flow, 1st Edition, February 2022, section 634.0404, equations 4-21 to 4-30 and Figure 4-8 (values of the Hazen-Williams coefficient, page 634-4.12). Values worked out by the EngiFormula engine.

Charts and diagrams

Energy line along the default pipe A pipe 500 ft long with the energy line sloping down along it. The drop over the length is the friction head loss, 10.72 ft, and its slope is the head loss divided by the length, 0.0214. Energy line Pipe, 500 ft Friction head loss 10.72 ft
The default case to scale in shape only: the energy line falls along the pipe by the friction head loss; its slope is the loss divided by the length.
Head loss over 500 ft against flow for three pipe sizes (C = 150) Three curves rise faster than a straight line, because the loss grows with the flow to the power 1.85, and the smaller the pipe the higher the curve. At 100 gpm the loss is 86.1 ft in a 2 in pipe, 12.0 ft in a 3 in pipe and 2.9 ft in a 4 in pipe. 087.5175262.5350 050100150200 Flow (gpm) Head loss over 500 ft (ft) 2 in 3 in 4 in
Three curves rise faster than a straight line, because the loss grows with the flow to the power 1.85, and the smaller the pipe the higher the curve. At 100 gpm the loss is 86.1 ft in a 2 in pipe, 12.0 ft in a 3 in pipe and 2.9 ft in a 4 in pipe.
Show chart data as a table
Head loss over 500 ft against flow for three pipe sizes (C = 150)
Flow (gpm) 2 in3 in4 in
20 4.390.610.15
40 15.812.190.54
60 33.474.651.14
80 577.911.95
100 86.1211.962.95
120 120.6716.754.13
160 205.4728.527.03
200 310.4743.110.62

Source: Calculated with the EngiFormula Hazen-Williams engine (method v1.0): h_f = 10.704 (Q/C)^1.85 L / D^4.87 in SI, with C = 150 (PVC, PE or HDPE). 1 US gallon = 231 in³, 1 foot = 0.3048 m exactly, from NIST Special Publication 811 (2008 edition), Appendix B.

Common uses

Water mains and distribution

Check the friction loss of a run at a design flow, with a C that allows for the age of the pipe.

Irrigation and plumbing

Find the loss of a lateral or a supply line, or the largest flow a pipe carries inside a loss you set.

Choosing a pipe size

Solve for the inside diameter that keeps the head loss under your limit, then pick the next size up from the maker’s table.

Seeing how age affects a pipe

Change the material from new to 30 years old and watch the loss rise: the C table shows by how much.

Checking another tool

The working shows each step, so you can compare the loss, the velocity and the pressure with a spreadsheet or a reference table.

Frequently asked questions

What is the Hazen-Williams equation?

It is an empirical formula for the friction head loss of water in a full pipe, built from measured flows in pipes. It uses the flow, the inside diameter, the length and one roughness number, the C factor. For 100 gpm through 500 ft of 3.068 in pipe with C = 150 it gives 10.72 ft.

How do you calculate head loss with the Hazen-Williams equation?

In SI units, hf = 10.704 × (Q ÷ C)1.85 × L ÷ D4.87. In the default case that is 10.72 ft over 500 ft, which is 2.14 ft per 100 ft, or 4.64 psi of pressure drop. The working under the calculator shows each step.

Which Hazen-Williams C factor should I use?

Pick the line of the table that matches the pipe and its age: 150 for PVC, PE and HDPE, 130 for new cast iron or steel, 120 at 5 years, 100 at 15 years, 80 at 30 years. These are typical values from the NRCS handbook, not exact ones. In the default case, C 120 instead of 150 raises the loss from 10.72 ft to 16.20 ft, so check the sensitivity table.

What is the difference between Hazen-Williams and Darcy-Weisbach?

Hazen-Williams uses one coefficient and works for water in turbulent flow. Darcy-Weisbach uses a friction factor that depends on the Reynolds number and the pipe roughness, so it works for any liquid and any flow regime. For the default pipe Darcy-Weisbach gives 10.32 ft against 10.72 ft here.

When does the Hazen-Williams equation not apply?

For liquids other than water, and when the flow is laminar or in the transition zone (Reynolds number below 4,000). The page shows the Reynolds number and warns when it is too low. The handbook gives no limit on pipe size or velocity.

Does Hazen-Williams include fittings and valves?

No. The equation gives the friction of the straight pipe. Elbows, valves and entrances are added as separate losses, for example with a loss coefficient K in the Pump Total Dynamic Head Calculator.

How do I convert head loss in feet to pressure drop in psi?

One foot of water head is about 0.433 psi (2.31 ft per psi), so 10.72 ft of head loss is 4.64 psi. The page shows both.

Is there a maximum velocity for the Hazen-Williams equation?

The NRCS handbook gives none. Fire-protection and water-supply rules set their own limits, so the page shows the velocity (4.34 ft/s here) and leaves the limit to you and the rules that apply.